Description of device parameters Waterpilot FMX21
102 Endress+Hauser
14.12 Expert→ Communication → HART config.
Burst mode
Write permission Service engineers/Expert
Description Switching burst mode on and off.
Options • On
• Off
Factory setting Off
Burst option
Write permission Service engineers/Expert
Description You can use this parameter to define which command is sent to the master.
Options • 1 (HART command 1)
• 2 (HART command 2)
• 3 (HART command 3)
• 9 (HART command 9)
• 33 (HART command 33)
Factory setting 1 (HART command 1)
Current mode
Write permission Service engineers/Expert
Description Configure current mode for HART communication.
Options • Signaling
Measured value transmission by the current value
• Fixed
Fixed current 4.0 mA (multidrop mode)
(Measured value transmission via HART digital communication only)
Factory setting Signaling
Bus address