Waterpilot FMX21 Commissioning
Endress+Hauser 43
Description
1 Select the "Pressure" measuring mode via the
"Measuring Mode" parameter.
Menu path: Setup → Measuring mode
L
WARNING
Changing the measuring mode affects the
span (URV)
This situation can result in product overflow.
If the measuring mode is changed, the
setting for the span (URV) must be
checked in the "Setup" operating menu and
readjusted if necessary.
i
p
A
B
A0017671
A See table, step 3.
B See table, step 4.
i Current value
p Meas.
2 Select a pressure unit via the "Press. eng. unit"
parameter, here "mbar" for example.
Menu path: Setup → Press. eng. unit
3 Select the "Set LRV" parameter.
Menu path: Setup → Extended setup → Current
output → Set LRV
Enter the value for the "Set LRV" parameter
(here 0 mbar) and confirm. This pressure value
is assigned to the lower current value (4 mA).
4 Select the "Set URV" parameter.
Menu path: Setup → Extended setup → Current
output → Set URV
Enter the value for the "Set URV" parameter,
here 300 mbar (4.5 psi), and confirm. This
pressure value is assigned to the upper current
value (20 mA).
5 Result:
The measuring range is configured for
0 to +300 mbar (0 to 4.5 psi).
9.10 Configuring level measurement
9.10.1 Information on level measurement
You have a choice of two methods for calculating the level: "In pressure" and "In
height". The table in the "Overview of level measurement" section that follows
provides you with an overview of these two measuring tasks.
The limit values are not checked, i.e. the values entered must be appropriate for the
sensor module and the measuring task for the device to be able to measure
correctly.
Customer-specific units are not possible.
The values entered for "Empty calib./Full calib.", "Empty pressure/Full pressure",
"Empty height/Full height" and "Set LRV/Set URV" must be at least 1% apart. The
value will be rejected, and a warning message displayed, if the values are too close
together.