Description of device parameters Waterpilot FMX21
86 Endress+Hauser
14.6 Expert → Measurement → Pressure
Set LRV
Write permission Operators/Service engineers/Expert
Description Set the pressure value, level or content for the lower current value (4 mA).
Factory setting • 0.0 % in Level measuring mode
• 0.0 mbar/bar or in accordance with ordering information in Pressure measuring mode
Set URV
Write permission Operators/Service engineers/Expert
Description Set the pressure value, level or content for the upper current value (20 mA).
Factory setting • 100.0 % in Level measuring mode
• URL Sensor or according to ordering information in Pressure measuring mode
Meas. pressure
Write permission No write permissions. Parameter is read only.
Description Displays the measured pressure after sensor trim, position adjustment and damping.
Pressure simulation value →
→
Meas. →
↓ ↑ ↓
Sensor → Sensor trim → Position adjustment → Damping → Electr. Delta P →
P
→ Level →
I
→ Current output
↓ ↓ ↓ ↓
Sensor pressure Corrected
press.
Corrected
Damping
Meas.
pressure
Sensor pressure
Write permission No write permissions. Parameter is read only.
Description Displays the measured pressure before the sensor trim.