Description of device parameters Waterpilot FMX21
90 Endress+Hauser
Write permission Operators/Service engineers/Expert
Description Enter the pressure value for the lower calibration point (vessel empty). See also "Empty
calib.".
Prerequisite • "Level selection" = In pressure
• "Calibration mode" = Dry -> entry
• "Calibration mode" = Wet -> display
Factory setting 0.0
Empty height
Write permission Operators/Service engineers/Expert
Description Enter the height value for the lower calibration point (vessel empty). The unit is selected
via the "Height unit" parameter.
Prerequisite • "Level selection" = "In height"
• "Calibration mode" = Dry -> entry
• "Calibration mode" = Wet -> display
Factory setting 0.0
Full calib.
Write permission Operators/Service engineers/Expert
Description Enter the output value for the upper calibration point (vessel full). The unit defined in
"Output unit" must be used here.
Note • For wet calibration, the level (e.g. empty or partially filled vessel) must actually be
present. The associated pressure is then automatically recorded by the device.
• In the case of dry calibration, the level (vessel full) does not have to be available. For the
"In pressure" level selection, the associated pressure must be entered in the "Full pressure"
parameter. The associated height has to be entered in the "Full height" parameter for the
"In height" level selection.
Factory setting 100.0
Full pressure
Write permission Operators/Service engineers/Expert
Description Enter the pressure value for the upper calibration point (vessel full). See also "Full calib.".