Waterpilot FMX21 Description of device parameters
Endress+Hauser 93
14.8 Expert → Measurement → Linearization
Lin. mode
Write permission Operators/Service engineers/Expert
Description Select the linearization mode.
Options Linear
The level is output without being converted beforehand. "Level before lin" is output.
Erase table
The existing linearization table is deleted.
Manual entry (sets the table to edit mode, an alarm is output):
The value pairs of the table (X-value and Y-value) are entered manually.
Semi-automatic entry (sets the table to edit mode, an alarm is output):
The vessel is emptied or filled in stages in this entry mode. The device automatically
records the level value (X-value). The associated volume, mass or % value is entered
manually (Y-value).
Activate table
The table entered is activated and checked with this option. The device shows the level
after linearization.
Factory setting Linear
Unit after lin.
Write permission Operators/Service engineers/Expert
Description Select volume unit, mass, height or % (unit of the Y-value).
Options %
cm, dm, m, mm
hl
in
3
, ft
3
, m
3
,
l
in, ft
kg, t
lb
gal
Igal
Factory setting %
Line-numb
Write permission Operators/Service engineers/Expert