Waterpilot FMX21 Description of device parameters
Endress+Hauser 99
Factory setting 22 mA
Set min. current
Write permission Operators/Service engineers/Expert
Description Enter lower current limit.
Some switching units accept no current smaller than 4.0 mA.
Options • 3.8 mA
• 4.0 mA
Factory setting 3.8 mA
Get LRV
Write permission Operators/Service engineers/Expert
Description Set the lower-range value – reference pressure is present at the device. The pressure for
the lower current value (4 mA) is present at the device. Use the "Confirm" option to assign
the lower current value to the applied pressure value.
Prerequisite: Pressure measuring mode
Options • Cancel
• Confirm
Factory setting Cancel
Set LRV
Write permission Operators/Service engineers/Expert
Description Set the pressure value, level or content for the lower current value (4 mA).
Factory setting • 0.0 % in Level measuring mode
• 0.0 mbar/bar or in accordance with ordering information in Pressure measuring mode
Get URV (pressure measuring mode)
Write permission Operators/Service engineers/Expert