EasyManua.ls Logo

Endress+Hauser WirelessHART Fieldgate SWG70 - Page 117

Endress+Hauser WirelessHART Fieldgate SWG70
138 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
WirelessHART Fieldgate SWG70 Modbus Interface
Endress + Hauser 117
Fig. 16-1: Mapping of Modbus registers Fieldgate SWG70
Refresh time Fieldgate SWG70 refreshes Modbus discrete inputs and input registers once every macro-
cycle. The length of the macrocycle depends on the number of WirelessHART devices in the
network, the response time of the devices and the number of parameters they transmit.
In general, shorter refresh times can be attained by restricting the traffic over the network
to essential parameters only.
0
65535
Coils
(not supported
by Fieldgate)
Discrete Inputs
Input registers
Holding registers
(in Fieldgate, an RO image
of the input registers)
1
65536
100001
165536
300001
365536
400001
465536
Register
Reference
address
RW
RO
RO
RW
0
65535
0
65535
0
65535

Table of Contents