Fieldgate configuration WirelessHART Fieldgate SWG70
50 Endress + Hauser
8.3 Interfaces (wired communication)
All Fieldgate SWG70 versions feature an Ethernet interface and a serial interface.
Depending on the device version, this interface can support different protocols.
See this section for information about the interfaces. For information about the protocols,
see Chapter 8.4 "Protocols (wired communication)" on page 52.
8.3.1 Ethernet
The parameters contained in this leaf pertain to the set up of the communication to the host
via Ethernet interface offered by Fieldgate SWG70.
1. Click Wired Communication => Interfaces => Ethernet to display the associated
parameters:
2. Enter the parameters, pressing Enter after each change.
Note: Automatic IP address assignment requires that there is a DHCP server in the
Ethernet network.
3. Press the Write Ethernet Information button when all parameters have been
changed.
The Fieldgate will restart with the new parameters.
If the IP address was changed, communication will be lost.
Change your computer's address if necessary and re-establish communication with
the new IP address.
If you are using the HART IP CommDTM, reconfigure the communication parameters,
before making connection again. See Chapter 7.3.2 "Adding the Fieldgate SWG70" on
page 38, Step 4.
Fieldgate
SWG70 version
Interface Protocol
Modbus EtherNet/IP HART AMS
SWG70-xx-1
Modbus
Ethernet X X X
Serial (RS-485) X X
SWG70-xx-2
Modbus + OPC
Ethernet X X X
Serial (RS-485) X X
SWG70-xx-3
EtherNet/IP
Ethernet X X X
Serial (RS-485) X