Diagnostics WirelessHART Fieldgate SWG70
58 Endress + Hauser
9.2.3 Burst Lists
Burst mode is a special mode of a HART slave device which allows it to periodically send the
response to a selected HART command without the being polled by the master. For a Wire-
lessHART slave device, it is the main operating mode. and can be used, for instance, to send
the process values from an adapter or connected HART device to Fieldgate SWG70 at regular
intervals.
The burst lists, contain information on the devices operating in this mode. The measured
values sent by the devices can be viewed in the Measurement List. See Chapter 11 "Addi-
tional Functions" on page 102.
1. Click on Diagnostics => Wireless Communication => Burst Lists:
Burst List parameters
Parameter Meaning
Instrument Identification Displays information identifying the device:
Long Tag: Long Tag of connected device
IO card: Identifier of fieldgate card used by the device
Channel: Identifier of card channel used by the device
Device Type: Designation of connected device
Status: Communication status of the associated device
Connected
Flashing: Devices connected, identification in progress
Continuous: Devices connected but not identified
Communication failure
Dev. Status: Device status of the associated device
Good
Out of specification
Failure
+/- Show/hide the burst list details
Burst Command Command number of selected burst commands with explanation:
1: Returns the primary value and units
2: Returns the loop current and its associated percent of range.
3: Returns the loop current and up to four predefined dynamic
variables and units (PV, SV, TV, QV)
9: Returns the value and status of up to eight device or dynamic
variables with units
48:Returns the complete device status information
77: Embeds the commands of a connected wired device so that they can be
transmitted by wireless
Num. Packets Number of burst messages sent by the network device since the last network
restart
Refresh Updates the burst list