Engineering WirelessHART Fieldgate SWG70
64 Endress + Hauser
10 Engineering
10.1 Instrument List
10.1.1 General
This leaf contains a list of instruments in the network. It is also possible to add individual
devices that are still to be connected.
1. Click on Engineering => Instrument List to open the dialog:
Instrument List
parameters
Parameter/Field Meaning
Instrument List Displays tabular information identifying the device:
Long Tag: Long Tag of connected device
IO card: Identifier of fieldgate card used by the device
Channel: Identifier of card channel used by the device
Device ID: HART serial number that is assigned at manufacturing time and that
differs for each HART device of a given type
Extended Device Type Code: Unique code identifying the HART product family
Delete button Deletes a device from the instrument list
Press Apply to register the change in Fieldgate SWG70
If the device is still communicating with the network, it will automatically
reappear in the list at the next refresh
Caution! Deleting a device from the instrument list can change the Modbus
register address if the Modbus addresses have been automatically generated.
Export/Export CSV Exports the current instrument list as a CSV file
Import/Import CSV Imports an instrument list that has been stored as a CSV file
Import Project Tree (DTM) In Offline Parameterize dialog, imports the network view to the Instrument List
Refresh Updates the instrument list
After switching on or resetting the device, wait at least one minute before
pressing the Reset button.
Apply Stores the current instrument list in Fieldgate SWG70