WirelessHART Fieldgate SWG70 Engineering
Endress + Hauser 87
1. Select a WirelessHART Adapter.
2. Open the folder "Burst Configuration" for the selected WirelessHART Adapter.
Every WirelessHART Adapter has its own "Burst Configuration" folder. The folder
contains the required "Burst OPC Data Items".
3. Activate the "Monitor" function for the folder "Burst Configuration".
4. Change to the folder "Data Monitor". The folder shows the current values of the "Burst
OPC Data Items".
5. Configure the "Burst OPC Data Items" according to your requirements.
For a description see Chapter "Description of the Burst OPC Data Items" on page 87
– Click on the "Burst OPC Data Item" that you want to configure.
– Select the client function "Sync Write" with a right click.
– Enter the new value. The newly entered value appears in the column "Value". Note that
the value has not been sent to the Fieldgate at this point.
– Repeat the procedure for every "Burst OPC Data Item" to be configured.
6. Set the "Burst OPC Data Item" StartConfiguration to the value "1" in order to transmit
burst configuration to the Fieldgate.
– Before transmission begins, the entered values are checked. If the values are invalid,
the transmission is stopped. The "Burst OPC Data Item" LastInfoMessage indicates
the error.
– If there are no errors, the "Burst OPC Data Item" LastInfoMessage displays the current
status.
– Once the burst has been successfully transmitted and activated, the "Burst OPC Data
Item" LastInfoMassage shows a message to this effect.
Description of the Burst OPC Data Items
Designation Meaning
BurstConfiguration.
BurstModeControlCode
(Burst-Modus)
Enter a number to switch the burst on or off.
• 0: Off
• 2: Wireless
BurstConfiguration.
CommandNumber
Enter the command number that is to be transmitted.
• Valid commands when the burst is for an adapter:
(MapSubDevice.DeviceIndex = 0): 1, 2, 3, 9, 33, 48
• Valid commands when the burst is for a field device
(MapSubDevice.DeviceIndex = from 1 to 4): 0 – 255
Check the field device manual for supported commands.
BurstConfiguration.
Device Variable.Variable1-8
If you use burst commands "9" or "33" or both, enter the appropriate codes for the
device variables. Codes for the WirelessHART-Adapter SWA70 are listed in see
Chapter "Device Variable Codes" on page 89. Check the appropriate manual for the
codes of other field devices.
• Device variables 1 – 8 are available for burst command "9".
• Device variables 1 – 4 are available for burst command "33".
BurstConfiguration.
LastInfoMessage
Displays information over the burst parameter set that should be or has been
transmitted. Possible information: error messages if the burst parameter set has
errors before transmission; status messages during transmission; a message
indicating successful transmission and activation of the burst.
BurstConfiguration.
MapSubDevice.DeviceIndex
Enter the device from which the burst command was transmitted.
• 0: Adapter
• 1: HART Subdevice 1
• 2: HART Subdevice 2
• 3: HART Subdevice 3
• 4: HART Subdevice 4
BurstConfiguration.
MapSubDevice.Message
Configures up to 10 burst messages.
Valid range: 1 – 10