WirelessHART Fieldgate SWG70 Engineering
Endress + Hauser 95
HART Device Map
Displayed information Description
HART Device Displays the HART device identifier.
This identifier is identical to the last 3 characters of the
device's HART descriptor. See Chapter 10.5.2.
Descriptor Displays the HART descriptor of the device.
The HART descriptor must comply with the dedicated
naming conventions. See Chapter 10.5.2.
Long Tag Name Displays the long tag name of the device.
HART Comm Fail This bit is flagged if a device is not available, e.g.
because it is not possible to establish the connection to
the device. Make sure that the maximum number of
HART devices in the "Module Definition" window is
greater than the actual number of HART devices.
Descriptor Not Unique This bit is flagged if the HART descriptor of the HART
device is not unique.
Change the HART descriptor using the associated HART
device DTM.
Data Burst Not Configured This bit is flagged if HART command 9 (alternatively
command 3 and 33) has not been flagged as burst in
the HART device.
Flag HART command 9 (alternatively command 3 or
33) using the associated device DTM. See
Chapter 10.5.3.
Cmd48 Burst Not Configured This bit is flagged if HART command 48 has not been
flagged by the HART device.
Flag HART command 48 using the associated device
DTM. See Chapter 10.5.3.