EQUIPMENT
(1) Opto-coupler output can be connected to DINLINE Alarm Relay (DAR275V) to provide Form C dry contacts.
*STATUS SENSE
*
WARNING
ERICO products shall be installed and used only as indicated in ERICO’s product instruction sheets and training materials. Instruction sheets are
available at www.erico.com and from your ERICO customer service representative. Improper installation, misuse, misapplication or other failure
to completely follow ERICO’s instructions and warnings may cause product malfunction, property damage, serious bodily injury and death.
Copyright ©2008 ERICO International Corporation. All rights reserved.
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.
www.erico.com
ANSI is a registered trademark of the American National Standards Institute. IEEE is a registered trademark of the Institute of Electrical and Electronics Engineers,
Incorporated. NEMA is a registered trademark of the National Electrical Manufacturers Association. UL is a registered trademark of Underwriters Laboratories, Inc.
Features
The TDF series has been specifi cally designed
for process control applications to protect the
switched mode power supply units on devices
such as PLC controllers, SCADA systems and
motor controllers. Units are UL
®
Recognized
and available for 3A, 10A and 20A loads and
suitable for 110-120V ac/dc and 220-240Vac
circuits.
The TDF is a series connected, single phase
surge fi lter providing an aggregate surge
capacity of 50kA (8/20μs) across L-N, L-PE,
and N-PE. The low pass fi lter provides up to
65dB of attenuation to voltage transients.
Not only does this reduce the residual
let-through voltage, but it also helps
further reduce the steep voltage rate-of-rise
providing superior protection for sensitive
electronic equipment.
• CRITEC
®
Transient
Discriminating
(TD) Technology
provides increased
service life
• In-line series
protection
• High effi ciency
low pass sine wave
fi ltering – ideal
for the protection
of switched mode
power supplies
• Three modes of
protection: L-N,
L-PE & N-PE
• 35 mm DIN rail
mount – simple
installation
• LED status
indication and
opto-isolated
output – for
remote status
monitoring
• CE, UL
®
1449
Ed. 3 Listed
CRITEC
®
Transient Discriminating Filter
TDF
LINE
Model TDF3A120V TDF3A240V TDF10A120V TDF10A240V TDF20A120V TDF20A240V
Item Number for Europe 700001 700002 700003 700004 700005 700006
Nominal Voltage, U
n
110-120 V 220-240 V 110-120 V 220-240 V 110-120 V 220-240 V
Distribution System TN-C-S, TN-S
Max Cont. Operating
Voltage, Uc
170VAC 340VAC 170VAC 340VAC 170VAC 340VAC
Stand-off Voltage 240V 400V 240V 400V 240V 400V
Frequency 0-60Hz 50/60Hz 0-60Hz 50/60Hz
Max Line Current, I
L
3 A 10 A 20 A
Operating Current @ U
n
135 mA 250 mA 240 mA 480 mA 240 mA 480 mA
Max Discharge Current,
I
max
10kA 8/20μs N-PE
20kA 8/20μs L-N
20kA 8/20μs L-PE
Protection Modes All modes protected
Technology In-line series low pass sine wave fi lter
TD Technology
Voltage Protection Level,
U
p
500V @ 500A
250V @ 3kA
700V @ 500A
600V @ 3kA
500V @ 500A
250V @ 3kA
700V @ 500A
600V @ 3kA
500V @ 500A
250V @ 3kA
700V @ 500A
600V @ 3kA
Filtering -62dB @ 100kHz -65dB @ 100kHz -53dB @ 100kHz
Status Green LED. On=Ok. Isolated opto-coupler output
Dimensions H x D x W:
mm (in)
90 x 68 x 72
(3.54 x 2.68 x 2.83)
90 x 68 x 144
(3.54 x 2.68 x 5.67)
Module Width 4 M 8 M
Weight: kg (lbs) 0.7 (1.54) 1.48 (3.25) 1.57 (3.46)
Enclosure DIN 43 880, UL94V-0 thermoplastic, IP 20 (NEMA
®
-1)
Connection 1 mm² to 6 mm² (#18AWG to #10)
Mounting 35 mm top hat DIN rail
Back-up Overcurrent
Protection
3A 10A 20A
Temperature -35°C to 55°C (-31°F to 131°F)
Humidity 0% to 90%
Approvals C-Tick, CE (NOM 3A, 120V), CSA 22.2, UL
®
1283,
UL
®
1449 Ed 3 Recognized Component Type 2
Surge Rated to Meet ANSI
®
/IEEE
®
C62.41.2 Cat A, Cat B, Cat C
Vendor Manual Surge Filter Alarm Relay Critec TDF-10A-240V