LIGHTNING PROTECTION FOR MASTS
7 (8)
Uppgjord (även faktaansvarig om annan) - Prepared (also subject responsible if other) Nr - No.
KL/ECS/S/LT Magnus Lindahl ECS/S/LT-96:5037
Dokansv/Godk - Doc respons/Approved Kontr - Checked Datum - Date Rev File
KI/ECS/S/LTC 1996-06-04 A
Error! Unknown switch argument.
High voltage input
See Figure 2.
The lightning protection system must be linked to the incoming neutral lead of the
electrical system. A terminal or busbar for this purpose must be available in the fuse
box. This terminal must be marked ”Lightning conductor earth”. The terminal must be
so placed in the electrical system that the functioning of any earth leakage trip circuit
breaker is not affected.
Figure 2. Mains power supply input with common neutral terminal for lightning
protection.