Product Specification for Power and Battery Cabinet
200 - 250 VAC ±10 % 50 Hz ±10 %
100 - 127 VAC ±10 % 60 Hz ± 8 %
200/100 - 240/120 ±10 % 60 Hz ± 8 %
The PBC will support installation with:
Single-phase (two-wire; earthed end of phase).
Single-phase (three-wire; earthed mid point).
Single-phase (three-wire; separate PE and N conductor).
according to TN, TT and IT power system
Output Supply Voltage
The PBC delivers the following output voltages:
RBS
Nominal + 24 V range 21.5-28 V
Nominal load current 5.2 A
AAU
Nominal -54.1 V range -42.8- -60V
Nominal load current 4.0 A
Link
Nominal -54.1 V range -42.8- -60V
Nominal load current 0.6 A
Power Consumption
Regarding Power Consumption figures see chapter General
Specification for RBS 2000 Micro Site Configuration.
Battery Backup
The PBC battery backup time is between 1.5–3 hours depending on
which configuration is used. The battery will be recharged within 24
hours.
For longer backup time an external UPS may be used.
6.7.10 Type Approval
Type Approval Standard
The PBC fulfils the required type approvals from: GSM 11.20 or GSM
11.21 standard JTC standard FCC rules and regulations. According to
requirements in Section Product Safety Requirements RBS 2000.
86 (306)
EN/LZT 123 2697 R5A
1998-08-13
© Ericsson Radio Systems AB