7.2 PSU DC/DC Kit
The PSU DC/DC kit is used for AMM 6p B or AMM 20p, converting +24 V DC to
–48 V DC with a maximum output power of 950 W. It consists of a sub-rack
(3U high), one or two Power Supply Units (PSU) and an FAU3. Two PSUs are
used for redundant power systems.
The +24 V DC external power supply is connected to the PSU front.
The sub-rack provides two –48 V DC connectors for PFU connection. Two
fused –48 V DC connectors for FAU1 connection are also available.
The sub-rack can be mounted in a standard 19" or metric rack or on a wall
using a dedicated mounting set.
EARTH
GROUNDING
FAU3
Fault
Power
-48VDC Power
Alarm
-48VDC OUT
A
B
00
01
-48VDC 0V
-48VDC 0V
3.15A
250V
3.15A
250V
-48VDC 0V
-48VDC 0V
+
PSU
Fault
Operation
Information
EC Bus
DC Out
DC In
+
PSU
Fault
Operation
Information
EC Bus
DC Out
DC In
FAU3
–48 V DC Out
(FAU1)
–48 V DC Out
(PFU1/PFU3)
–48 V DC Out
(PFU1/PFU3)
+24 V DC In
PSU
Fan alarm
(NPU1 B)
8261
Figure 97 PSU DC/DC kit
7.2.1 Cooling
Forced air-cooling is always required and provided by FAU3, which holds two
internal fans. It is power supplied by an internal pre-assembled cable connected
to the front. A connector for alarm export to the NPU1 B is also available.