Note:
1. A single-phase servomotor should apply a two-phase filter. A three-phase servo drive should apply a
three-phase filter.
2. Choose the right filter according the specifications of operating voltage, current, and manufacturer.
(2) Precautions on Using Noise Filters
Do not put the input and output lines in the same duct or bundle them together.
x
Noise
Filter
Ground plate
Separate these circuits
Noise
Filter
Noise
Filter
Noise
Filter
Ground plate
Ground plate
Ground plate
Separate the noise filter ground wire from the output lines.
Do not accommodate the noise filter ground wire, output lines and other signal lines in the same duct or bundle them
together.
X
Noise
Filter
Ground plate
Noise
Filter
Ground plate
Connect the noise filter ground wire directly to the ground plate. Do not connect the noise filter ground wire to other
ground wires.