External Torque Limit Reference Signals
The /P-CL (Forward External Torque Limit) and /N-CL (Reverse External Torque Limit) signals are used
as the external torque limit reference signals. The /P-CL signal is used for the forward torque limit and the
/N-CL signal is used for the reverse torque limit.
Allocated by
Pn509 or
Pn510
Applies the forward external torque limit.
The torque is limited to the smaller of the
settings of Pn401 and Pn403.
Cancels the forward external torque limit.
The torque is limited to the setting of Pn403.
Applies the reverse external torque limit.
The torque is limited to the smaller of the
settings of Pn402 and Pn404.
Cancels the reverse external torque limit.
The torque is limited to the setting of Pn404.
Setting the Torque Limits
If the setting of Pn401 (Forward Torque Limit), Pn402 (Reverse Torque Limit), Pn403 (Forward External
Torque Limit), or Pn404 (Reverse External Torque Limit) is too low, the torque may be insufficient for
acceleration or deceleration of the Motor.
Forward Internal Torque Limit
Reverse Internal Torque Limit
Forward External Torque Limit
Reverse External Torque Limit
Changes in the Output Torque for External Torque Limits
The following table shows the changes in the output torque when the internal torque limit is set to 300%.
In this example, the Motor direction is set to Pn001.0=0 (Use CCW as the forward direction).