Summa Series Servodrive Product Manual
Trial Operation
Document Version: V1.01
(Dec, 2019)
© 2019 ESTUN Automation Co., Ltd. All right reserved.
8-10
8.5.5 Operation Procedure
Use the Panel Operator of the Drive
Before performing the Program Jogging (PJOG) operation by using the Panel Operator, you shall check
and set the following parameters properly.
WARNING
Check and set the parameters Pn164 to Pn171 as proper values in advance,
and ensure the movable parts have sufficient travel in the forward and
reverse directions.
For the method of checking and setting parameters by using the Panel Operator, refers to the section 4.1.4
Parameter Setting Mode.
The following are the steps to run the Motor between the two programmed operation patterns (PJOG0 and
PJOG1).
Step 1 Press [M] key several times to select the Utility Function Mode.
Step 2 Press [▲] key or [▼] key to select the function number Fn018.
Step 3 Press [◄] key, and Panel Operator displays as below.
Step 4 Press [M] key to execute this operation, and Panel Operator displays as below.
Step 5 Press [◄] key to return to the display of the Fn018.
Use the ESView V4
The Motor can be run between the two programmed operation patterns (PJOG0 and PJOG1) by executing
PJOG function.
Step 1 Select Run > PJOG in the Menu Bar of the ESView V4 main windows.