Summa Series Servodrive Product Manual
Document Version: V1.01
(Dec, 2019)
© 2019 ESTUN Automation Co., Ltd. All right reserved.
Free-Run (ESC register0x981: 0x980 = 0x0000)
In Free-Run mode, the local cycle is independent from the communications cycle and master cycle.
DC Mode (ESC register0x981: 0x980 = 0x0300)
In this mode, the Drive is synchronized with the host controller (master) on the Sync0 event.
The following figure gives a timing chart for DC synchronization.
Frame U
Master application task
Master application task
Frame U
Master user
shift time
Master application task
Frame U
U
Sync 0 shift time
UU
Cycle time (1C32-02h)
Sync 0
event
Shift time (1C33-03h)
U
Cycle time (1C32-02h) Cycle time (1C32-02h)
Shift time (1C33-03h)
Network
Master
Slave
Input Latch Output Valid
Sync 0
event
Sync 0
event
NOTE: Only the object 1C33-03h can be set.
5.4 Communication Indication
5.4.1 Indicator Lamps on Panel Operator
There are 3 indicator lamps on the panel Operator of the Drive to indicate the communication status of
EtherCAT: SYS, RUN and ERR.
M ▲ ▼ ◀
SYS: System indicator lamp
RUN: Running indicator lamp
ERR: Error indicator lamp
SYS RUN ERR
POWER
SYS Indicator
The SYS indicator shows the system status of EtherCAT communications.
No power supplied or EtherCAT is resetting
Initialization is complete and EtherCAT is
operating normally