6.4 Menu StAt (Only for display LED)
If the StAt voice is chosen from the general menu, several main statuses of the system are displayed (can be navigatedwith the
Left/Right buttons) on the reference page:
Exampletable of system statuses displayed on Page 1
Reference page Status displayed System status
Page 1 Unit Indicates the status in which the machine operates (OFF, ChIL, pdC, dEFr, dRIp, F-C)
Page 1 ModE Indicates the operational mode of the machine (ChIL, pdC)
Page 1 tdF1 Accumulation of wait time for defrost circuit 1
Page 1 dFr1 Duration of circuit defrost 1
Page 1 tdF2 Accumulation of wait time for defrost circuit 2
Page 1 dFr2 Duration of defrostcircuit 2
Page 1 SEtC Summer mode current set point
Page 1 SEtH Winter mode current set point
Page 1 rEGP Main regulation probe
Page 1 PREq Power required [%]
Page 1 PSup Power supplied[%]
Example table of system statuses displayed on Page 2
Reference page Status displayed System status
Page 2 CMP1, CMP2 .. CMP6 Status of compressors (dIS, OFF, tOn, On, tOFF, ALAr, MAnU)
Page 2
FAn1, FAn 2 Status of fans (dIS, OFF, tOn, On, tOFF, ALAr, MAnU)
Page 2
InF1,InF2 Speed of condenser fans [%]
Page 2
PMP1, PMP2 Status of pumps (dIS, OFF, On, ALAr, MAnU)
Page 2
PMS1, PMS2 Status of heat source pumps (dIS, OFF, On, ALAr, MAnU)
Page 2
F-C Status of free-cooling activation
Page 2
vF-C Free-cooling valve
Page 2
FF-C Free-cooling regulation
Page 2
vpC1 Status of C1splitter valve for free-cooling
Page 2
vpC2 Status of C2 splitter valve for free-cooling
Sample table of system statuses displayed on Page 3
Reference page Status displayed System status
Page 3 tExt External temperature probe
Page 3
tAux Remote temperature probe
Page 3
tiFc Machine input temperature probe (Free-Cooling)
Page 3
tin Heat sink exchanger input temperature probe
Page 3
toC1/2 Heat sink exchanger output temperature probe (circuit 1,2)
Page 3
toS1/2 Heat source exchanger input temperature probe (circuit 1,2)
Page 3
tCo1/2 Coil temperature probe (circuit 1,2)
Page 3
GAS1/2 Exhaust gas compressor temperature probe (circuit 1,2)
Page 3
tSu1/2 Intake compressor temperature probe (circuit 1,2)
Page 3
PCO1/2 Condensing pressure probe (circuit 1,2)
Page 3
PEV1/2 Evaporation pressure probe (circuit 1,2)
Page 3
Pun1/2 Single pressure probe (circuit 1,2)