OS3030 Changing and Scanning the Basic Values
7. Output function parameters
27
7.10
Additional program
Additional program time
In this programming step,
specify the length of the
Additional program; the
permissible range is
0...999 minutes. The Additional program time applies for the phase se-
lected. It is interrupted early if you switch to another phase (production,
standby, rinse or maintenance) and the Additional program has not been
selected for that particular phase.
WARNING! If you set the time to 0 minutes, the Additional program runs
from the start of the selected phase to the end.
Additional program time delay
The start of the Additional
program can be delayed
by 0 to 999 seconds.
Permeate valve
Conductivity limit
The switching of the per-
meate valve is dependent
on conductivity during the
production phase. You
can define a set of between 0.2 and 6500.0 µs/cm.
Permeate valve activation delay
The activation of the
permeate valve can be
delayed if the limit is ex-
ceeded. The delay can be
set to 0 to 999 seconds.
Permeate valve deactivation delay
The drop-out of the per-
meate valve can be de-
layed if the value drops
below the threshold. The
delay can be set to 0 to 999 seconds.
Alarm relay
Activation of alarm signal 1
In this and in the subse-
quent two steps, program
the events which should
trigger off the alarm relay.
Warning: You can only select the options for which limits have been set in the previous pro-
gramming steps, for which an input function has been selected or with fixed input functions.
(EM, FU and PS).
Press INFO to see the meaning of the abbreviation in plain text.
MI = Value < min. conductivity limit EM = Tank is empty
MA = Value > max. conductivity limit FU = Tank is full
S t e p n o . : 7 . 4
A d d . p r o g r a m 2 0 m
S t e p n o . : 7 . 5
D e l a y a d d
. p r 1 0 s
S t e p n o . : 7 . 6
L i m i t C M 8 0 . 0
S t e p n o . : 7 . 7
R i s e d e l a y 2 s
S t e p n o . : 7 . 8
F a l l i n g D e l a y 1 0 s
S t e p n o . : 7 . 9
M I - M A - E
M - F U
-