OS3030 Changing and Scanning the Basic Values
9. "Production phase"
29
9. "Production" phase
The production phase comprises 3 time-dependent stages which run in con-
secutive order. The system remains in the subsequent stage 4 position until
the production phase has ended. If production is over and the pressure pump
is in operation, the system remains in this position for a further 3 seconds
before the pump starts running.
You define whether the input valve and the concentrate valve are open during
these 4 stages, and when the pressure pump kicks in.
In the case of equipment with an IF plug-in card, you also specify whether the
output relay is activated for each of the output functions selected in pro-
gramming steps 6.1 and 6.2.
If the "permeate valve" function has been selected in step 9.7, the valve con-
trol is dependent on conductivity during the "production" phase.
Set the time of the first
stage. The permissible
range is 0 to 999 seconds.
If you select 0, the stage is
skipped.
Specify which valves are
open, whether the high-
pressure pump is running
and whether the pro-
grammed OUT1 and OUT2 outputs, if present, are active. The functions pro-
grammed in programming steps 6.1 and 6.2 are active for these outputs.
Press INFO to see the meaning of the abbreviation in plain text.
PU = High-pressure pump PV = Permeate valve
IV = Input valve DO = Dosing
CV = Concentrate valve AP = Additional program
Set the time of the second
stage. The permissible
range is 0 to 999 seconds.
If you select 0, the stage is
skipped.
Program the values in ac-
cordance with programming
step 9.2
Set the time of the third
stage. The permissible
range is 0 to 999 seconds.
If you select 0, the stage is
skipped.
Program the values in ac-
cordance with programming
step 9.2
Program the values in ac-
cordance with programming
step 9.2..
The system remains in this
position until production is over.
S t e p n o . : 9 . 1
P r o d u c t i o n 1 6 0 s
S t e p n o . : 9 . 2
P U - I V | C V - P
V - D O
-
S t e p n o . : 9 . 3
P r o d u c t i o n 2 0 s
S t e p n o . : 9 . 4
P U - I V | C V - P
V - D O
-
S t e p n o . : 9 . 5
P r o d u c t i o n 3 0 s
S t e p n o . : 9 . 6
P U - I V | C V - P
V - D O
-
S t e p n o . : 9 . 7
P U | I V | C V - P
V - D O
-