CT70-EN-V8.2-4/12
5
The Voltage menu displays the True RMS line voltage. Use the button to scroll the Voltage sub-
menu (line voltage, ground-to-neutral voltage, Peak Voltage (P), and Frequency (Hz)).
The Voltage Drop (Vd) window indicates percent voltage drop (with 15A load) and the Loaded
Voltage (Vl). The voltage drop sub-menu offers a load voltage result for 20A and 12A loads. Use the
button to scroll the sub-menu.
The Impedance (Z) window indicates the impedance in ohms of the hot conductor. The impedance
sub-menu displays the neutral (N) and ground (G) conductor impedances. Use the button to move
through the sub-menu.
Note that testing ground impedance will trip a GFCI circuit.
The ASCC window indicates the Available Short Circuit Current that the branch current can move
through a breaker in a short circuit situation.
GFCI Button
The GFCI (Ground Fault Circuit Interrupt) feature performs two tests:
GFCI: Faults a circuit when 6 to 9mA from hot to ground is detected
EPD (Equipment Protective Device): For breakers equipped with an EPD, the breaker trips for
ground faults greater than 30mA.
To display the GFCI main menu window, press the GFCI button. To toggle the two tests use the
button. Once the desired test is selected, press the GFCI button to start the test. These tests are
further detailed below.

Other manuals for Extech Instruments CT70

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Extech Instruments CT70 and is the answer not in the manual?

Extech Instruments CT70 Specifications

General IconGeneral
BrandExtech Instruments
ModelCT70
CategoryCircuit Tester
LanguageEnglish