11 BASIC programming fw version 1.6 or higher
BASIC Function Default
dF
DEFAULT configuration
It displays whether the board is configured to factory set-
tings (default).
Y = the board is configured in default
no = at least one value has been modified with respect
to default
If you wish to reload all default settings, set
Y.
Y
Ln
LEAF NUMBER
1 = 1 leaf
2 = 2 leaves
1
If the function is modified, SETUP must be performed.
PO
PARTIAL OPEN
Set the opening percentage in Partial operating mode
no= 100% opening
Adjustable from 20% to 95% (MAX) of complete opening
Step = 5%
The minimum width prescribed by the cur-
rent legislation on escape routes must be
respected when adjusting this percentage.
no
PA
PAUSE TIME
This allows you to adjust the pause time of the fully open door.
Adjustable from
0 to
30 s.
Step = 1 s
02
The pause time is only active in automatic operation mode.
ES
Energy Saving
no = not enabled
Y = enabled
no
Pn
NIGHT PAUSE TIME
In night-time mode, if opening is done with the Key com-
mand, the door remains open for the time set with this
function.
Adjustable from
0 s to
4 minutes (MAX).
from
0 to
58 s, step = 2 s; time displayed in seconds.
from
58 s to
4.0 minutes, step = 10 s; time displayed in
minutes.tens of seconds: e.g.
1.2 = 1 minute and 20 seconds.
10
CS
CLOSING SPEED
Adjustable from
1 (minimum) to
10 (MAX).
03
OS
OPENING SPEED
Adjustable from
1 (minimum) to
10 (MAX).
10
CF
CLOSING FORCE
Adjustable from
1 (minimum) to
10 (MAX).
03
tF
PUSH TIME on OBSTACLE
Adjustable from
0.1 s to
3.0 s.
Step = 0.1 s
1.0
BASIC Function Default
Id
INTERNAL DETECTOR INPUT
no = internal detector not enabled
Y = internal detector in current
Y
(
*
)
Ed
EXTERNAL DETECTOR INPUT
no = external detector not enabled
1 = external detector with contact in frequency
2 = external detector in current
3 = internal detector in current
4 = external detector with N.O. contact
5 = external detector with NC contact
4
(
*
)
E1
OPEN EMERGENCY CONFIGURATION
no = not enabled
nO = input with NO contact
nC = input with NC contact
nO
(
*
)
St
EXIT PROGRAMMING
It lets you exit programming, and decide whether to save or
not the modifications made.
Y = save (only if there are NO configuration errors)
no = do not save
Press F to confirm. After exit, the display shows automation
status:
00 CLOSED
01 OPENING
02 OPEN
03 In PAUSE
04 in NIGHT-TIME PAUSE
05 CLOSING
06 OPEN in EMERGENCY
07 in MANUAL mode
08 in NIGHT-TIME mode
09 OPENING with AUX Motor
10 System TEST in progress
11 STANDBY
12 Safety TEST in progress
13 OPEN in ERROR
LO-L2 PHASES LO, L1, L2 SET-UP IN PROGRESS
Y
12 ADVANCED programming fw version 1.6 or higher
ADVANCED Function Default
P1
SAFETY INPUT CONFIGURATION S1
no = no device
Co = safety on closure with NO contact
Cc = safety on closure with NC contact
Oo = safety on opening with NO contact
Oc = safety on opening with NC contact
no
(
*
)
1F
SAFETY INPUT TEST S1
Not displayed if
PI =
no
Y = test enabled
no = test not enabled
Y