Timers
Operation of the TRS input in this mode
If a leading edge is produced at the TRS input at any moment during timing or afterwards, the PLC
initializes the timer, assigning the value 0 to its T status and cancelling its count (it initializes this
to 0). Due to the fact that the timer is initialized, it will be necessary to activate its trigger input to
activate it again.
Operation of the TEN input in this mode
If once the timer has been activated, TEN = 0, the PLC interrupts the timing and TEN must be set
to "1" to resume timing.