Central unit
Connector X3.
37-pin female connector of the SUB-D type used for the PLC outputs.
Both 24V and 0V of the power supply used to power these PLC outputs must be connected to pins
18 and 19 (for 0V) and pins 1 and 20 (for the 24V) of the connector.
All shields must only be connected to ground at the CNC end leaving the other end free. The wires
of the shielded cable must not be longer than 75 mm without the protection shield.
Pin Signal and function
1
2
3
4
5
24 V
O33
O35
O37
O39
External power supply.
6
7
8
9
10
O41
O43
O45
O47
O49
11
12
13
14
15
O51
O53
O55
O57
O59
16
17
18
19
20
O61
O63
0 V
0 V
24 V
External power supply.
External power supply.
External power supply.
21
22
23
24
25
O34
O36
O38
O40
O42
26
27
28
29
30
O44
O46
O48
O50
O52
31
32
33
34
35
O54
O56
O58
O60
O62
36
37
O64
Chassis - Shield.