·76·
Installation manual
CNC 8055
CNC 8055i
2.
CNC 8055 I CONFIGURATION
SOFT: V02.2X
CNC structure
Enclosure
The minimum distance from each side of the monitor to its enclosure in order to guarantee the
required ambient conditions is shown below:
It is up to the installer to make sure that the enclosure has forced ventilation or ventilation grooves
in order to prevent the inside temperature to exceed the specified ambient temperature.
Between 5º C and +50º C (41º F and 122º F)
Relative humidity between 5% and 95% non condensing
When using a fan to better ventilate the enclosure, a DC fan must be used since an AC fan may
generate electromagnetic interference resulting in distorted images being displayed by the CRT.
Brightness and contrast may be adjusted on monochrome monitors. See the Operating manual,
chapter on Diagnosis, section on Hardware configuration.