Hardware configuration.
CNC 8070
MONITOR-21 MULTITOUCH.
9.
Enclosure and mounting of the module.
·189·
(REF: 1911)
9.4 Enclosure and mounting of the module.
9.4.1 Enclosure design.
The enclosure must meet the following requirements:
• The degree of protection of the enclosure must be IP54, according to standard IEC
60529.
• Keep the enclosure clean.
• The dissipation surface of the enclosure must be enough to evacuate (by convection)
the heat generated inside.
• In the connector area, reserve a space that allows the cables to be connected, respecting
their radius of curvature.
• Respect the minimum distances recommended between the enclosure walls and the
hardware to let the air flow and improve heat dissipation.
Dimensions of the cut off part and the enclosure.
To meet the previous requirements, Fagor recommends the following.
• The enclosure must not have any ventilation holes, because they could let dust or other substances
in.
Before building an enclosure with glass fiber u another poor heat dissipating material, contact Fagor
Automation.
mm inch
W 550,30±1,0 21,67±0,040
H 341,80±0,7 13,46±0,025
(*) Minimum recommended distance.
mm inch
D (*) 75 2.95
H
W
D
Radius of the corners = 5 mm (0.2 inches).