Hardware configuration.
CNC 8070
16.
CNC-FPS. FAGOR-UPS (Q7-A PLATFORM ONLY).
UPS Connection Diagram.
·262·
(REF: 1911)
16.5 UPS Connection Diagram.
Jumper terminals.
• The R1-R2 terminals are jumpered at the factory: to connect the UPS to the CNC, the
jumper must be removed.
• The 13-23-33-24V terminals are jumpered at the factory: to connect the UPS to the CNC,
there is no need to remove the jumper.
Connection to the CNC and to the power supply.
The R1-R2 connector of the UPS is a free of potential relay. Both signals can go to any
DISSABLE_BAT pin of the CNC (never both signals to the same pin).
Cable characteristics.
I65
BAT_MODE
DISABLE_BAT
DISABLE_BAT
UPS. CNC.
A22
24 V
GND
+
–
Output.
24 V power supply.
+
–
+
–
Output. Input.
34
R1
R2
24
14
Cable data.
Minimum/maximum tightening torque. 0.5 / 0.6 Nm.
Minimum/maximum section. 0.2 / 2.5 mm².
Minimum/maximum AWG section. 24 / 12.
Length to be stripped.
(use ferrules on flexible wires/cables).
7 mm.