Hardware configuration.
CNC 8070
6.
CENTRAL UNIT + MONITOR (Q7-A PLATFORM).
Specifications.
·96·
(REF: 1911)
The machine manufacturer must comply with the EN 60204-1 (IEC-204-1) regulation
regarding electrical shocks in case of defective input/output pins with external power supply
when not plugging the connector before turning the power supply on.
Ambient. • Storage and transport temperature:
- Between -40 ºC (-40 ºF) and +70 ºC (158 ºF).
• Work temperature:
- Between 5 ºC (41 ºF) and 55 ºC (131 ºF).
• Temperature outside cabinet:
- Between 5 ºC (41 ºF) and 45 ºC (113 ºF).
• Temperature inside the enclosure:
- Less than 55 ºC (131 ºF).
• Relative humidity:
- 20 ~ 85% RH without condensation.
• Pollution degree 2.
• Maximum work altitude:
- The unit must work properly at 2000 m according to IEC 61131-2.
• Vibration test according to IEC 60068-2-6 with a frequency step of 1
octave/minute (±10%) and a duration of 10 sweeps.
-5 Hz f 8.4 Hz; movement of constant 3.5 mm amplitude (peak value).
-8.4 Hz f 150 Hz; 1g acceleration and constant amplitude (peak value).
• Degree of protection:
- IP65 (front), IP20 (rear).
Power supply. • Use a regulated 24 V DC power supply (between -15% and +20%) and 2 A
(including voltage ripple and noise). The power supply must meet the
UL1950 standard.
Connectivity. • 3 USB 2.0 ports, (one accessible at the front, protected by a cover).
• 1 USB 3.0 port
• 1 RS-232/422/485 (115 kbps) serial port (optional).
• 1 Ethernet port for 10/100/1000 BaseT connection.
• CAN Bus (CANfagor/CANopen).
• Sercos II bus.
• EtherCAT bus.
Inputs/outputs. • 16 opto-coupled digital inputs (24 V DC).
- IEC61131-2 type 1 and type 3 compliant.
• 8 opto-coupled digital outputs (24 V DC, 500 mA).
- ON cycle: minimum 75 µs (25 µs, optional in two of them).
• 1 analog outputs (±10 V, 16-bit resolution).
• 1 feedback inputs (5 V, 250 mA).
- Incremental TTL signal, differential TTL or 1 Vpp.
- Frequency : 100 kHz (TTL), 1000 kHz (TTL differential) / 500 kHz (1 Vpp).
• 1 relay with one normally open contact (1A at 24V).
• 2 probe inputs (5 V or 24 V)
• 1 entry for UPS unit control.
• 1 input for three handwheels with A and B signals (5 V DC TTL)
(only C70-10K).
Type. Description.
To help increase storage space, Fagor Automation lists several CFast cards in its catalog; when using
a third-party CFast, always use an industrial grade CFast SLC as these support temperatures from
between -40ºC and +85ºC (-40 ºF and 185 ºF) and can last five years with constant day-to-day writing.
Fagor Automation shall not be held responsible for any problems caused by using lower-quality CFast
cards.
Do not run part programs from a USB port, whether it be while using a pendrive or external hard drive.
Fagor Automation recommends using the USB port only to exchanging data, such for programs,
reports, etc. If you require more storage space, then use a CFast disk.
DO NOT connect any kind of hub to the USB port.