Installation
8.
INSTALLATION
System installation
302
Ref.2003
· 248 ·
QC-PDS
HARDWARE
A18. Under cover +24 V DC terminals.
For power supplies, drives, bus protection modules and capacitor
modules.
X14. Basic control signals.
For QC-PS-
non-regenerative power supplies.
X5. Software transfer and/or adjustment process of the axis through a
RS-232 serial line from the WinDDSSetup application for a PC or laptop.
Only for the QC-DR-275-SS2 drive and QC-RPS-160-SN0 main power
supply
X13A. Feed axis or spindle STO · Safe Torque Off · for single-drives.
X13A/X13B. STO for each feed axis or spindle · Safe Torque Off · for
dual-drives.
X33. Soft-Start activation.
For a QC-APS3-15 auxiliary power supply.
X34. SBC for the feed axis brake · Safe Brake Control ·
For the QC-DR-275-SS2 drive.
X35. Basic control signals
For the QC-RPS-160-SN0 regenerative power supply.
X60. Line voltage feedback.
For regenerative main power supplies.
Connection to the central point of the protective earth.
For each of the chassis of the units that make up the entire QC-PDS
system.
Electrical precautions
MANDATORY. For protection against high leak currents (3.5 mA AC or
10 mA DC), use a protective earth conductor with a cross-section of at
least S/2, where S (mm²) is the cross section of the conductors connected
to the power supply terminals.
For S (mm²) that are up to and including 35 mm², use a protective earth
conductor with a cross section of at least 10 mm² (Cu) or 16 mm² (Al) or
two protective earth conductors with the same cross section as that of the
wires connected to the power supply terminals.
When making protective earth connections, ensure to comply with local
standards. Note the symbol indicating this precaution indicated by an
arrow in figure F. H8/9.
F. H8/9
Precaution against high leakage currents. Warning symbol on the upper part of
the units.
WARNING. The system must always be installed before applying voltage
according to the EN 60204-1 standard. Ignoring it may cause serious
injuries, even death.