Power supplies
POWER SUPPLIES
Regenerative Power Supplies
2.
Ref.2003
· 67 ·
QC-PDS
HARDWARE
X60 connector.
Line voltage feedback
3-pin connector located on top of the unit and identified as X60.
The aerial plug-in connector has screw-on connection and a lock and
release lever is supplied as an accessory. It is used to connect the line
input phases to reference (with the identical sequence) the input phases in
the main regenerative power supply.
The following table shows the main data of the aerial connector and the
wire to be connected:
Pinout
The pinout is printed on the connector as T1-T2-T3.
Installation
See section, for further details on this installation, see chapter 6. POWER
LINE CONNECTION of this manual.
Connector data
Nr of poles 3
Gap (mm) 7.62
Min./max. tightening torque (N·m) 0.5/0.6
Flat screwdriver, size (mm) 0.6 x 3.5
Max. current (A) 0.5
Min. admissible cross-section (mm²)
1
Max. cross-section (mm²)
2.5
Connection data
Length to strip (mm) 8
Min./max. cross-section of solid conductor (mm²) 1/2.5
Min./max. cross-section of flexible conductor (mm²) 1/2.5
Min./max. cross-section of flexible conductor,
with a ferrule and without a plastic sleeve (mm²)
1/2.5
Flexible conductor cross-section with a ferrule,
with plastic sleeve (mm²)
1/2.5