Power supplies
80
2.
POWER SUPPLIES
Regenerative Power Supplies
· 68 ·
Ref.2003
· 68 ·
QC-PDS
HARDWARE
X35 connector
Basic control signals
6-pin connector located on the front of the unit and identified as X35.
Aerial male plug-in connector with spring «push-in» connection supplied as
an accessory. It is used to carry out basic control functions with input and
output signals.
The following table shows the main data of the aerial connector and the wire
to be connected:
Pinout
Pin description
Installation
See section, 8.6.10 CONNECTIONS FOR BASIC CONTROL SIGNALS.
NOTE. Only available at the QC-RPS-160-SN0 model.
Connector data
Nr of poles 6
Gap (mm) 2.5
Section (mm²) 0.5
Connection data
Length to strip (mm) 8
Cross-section of solid conductor (mm²) 0.5
Cross-section of flexible conductor (mm²) 0.5
Cross-section of flexible conductor, with a ferrule
and without a plastic sleeve (mm²)
0.5
Length of socket (mm) 10
F. H2/21
X35 connector. Pinout.
T. H2/16
X35 connector. Pin description.
Pin Signal Description
1
ERROR RESET
System error RESET input.
UN: 24 V DC; I: 4.5-7.0 mA; Umax.: 33 V DC
2
SPEED ENABLE
General system speed enable.
UN: 24 V DC; I: 4.5-7.0 mA; Umax.: 33 V DC
3
RPS ENABLE
Enabling input for the DC BUS voltage.
UN: 24 V DC; I: 4.5-7.0 mA; Umax.: 33 V DC
4
GND
0 V reference of the digital inputs:
ERROR RESET - pin 1 -
SPEED ENABLE - pin 2 -
RPS ENABLE - pin 3 -
5
SYSTEM OK
Normally open (N. O.) relay contact that
indicates the unit status.
Opening of the case of failure.
UN: 24 V DC / 18 V AC;
Umax.: 33 V DC / 24 V AC; Imax.: 1 A
6
SYSTEM OK
ERROR RESET
SPEED ENABLE
RPS ENABLE
GND
SYSTEM OK
SYSTEM OK
1
2
3
4
6
5
6
1