Continued from page 4
-8-
-6--5- -7-
4.3 DELETION – removing entries
Confirm by pressing OK. The cell will be deleted. The timer will display the
next programmed cell number. Pressing MENU will take you to the root level.
PLEASE NOTE!
To erase all previous ON-OFF COMMANDS settings see section 5.6.
Accept by pressing OK. The timer will enter work mode menu (auto – hand).
With +/- keys select desired operation mode:
4.4 OPERATION MODE
Using the +/- keys select “mode”.
*MANUAL – “hand”
*AUTOMATIC – “auto”
Accept by pressing OK. The timer will automatically exit the operation mode
selection and go to the program menu. Pressing Menu one more time will
take the timer back to the root menu.
PLEASE NOTE!
To change the contact position in the MANUAL OPERATION mode use the +/-
keys at the root level. In the absence of any program entries timer will
automatically run in MANUAL MODE (there is no option to set AUTOMATIC
OPERATION MODE).
5.1 Automatic time change – dst
Confirm by pressing OK. The timer will enter the System Settings submenu
(dst - utc - batt - cal - lcd - clear - info). Select the parameter with the +/- keys
and confirm with OK. Pressing MENU will take you to the upper level.
5. SYSTEM SETTINGS
Press MENU. The timer will enter the program menu. Using the +/- keys
select system settings “syst”.
DST – Daylight Saving Time – international name of summer time. Confirm by
pressing OK. The timer will enter the menu with the option to disable
automatic time change (auto-off). With +/- keys select desired mode:
* with AUTOMATIC TIME CHANGE – “auto”
* without AUTOMATIC TIME CHANGE – “off”
5.2 Time zone – utc
Using the +/- keys select ON-OFF COMMANDS reset mode "del".
Press OK to accept. The timer will enter the memory cell number selecting
mode. Select the cell to be deleted and accept by pressing OK. The timer will
be waiting for confirmation. This is indicated by alternating flashing of the
number of the selected cell and its set parameters.
Mo
TU
WE
TH
FR
SA SU
ş
1
ON
OFF
1
1 1
Confirm by pressing OK. The timer will enter the submenu (prog - sys - error).
Use the +/- keys to select reset option:
* "prog" – deletion of ON/OFF entries
* "sys" – deletion of system settings
Confirm by pressing OK.
A. prog
Confirm selected option by pressing OK. The timer will enter standby mode
awaiting for deletion confirmation. This is indicated by alternating flashing
of "prog" and "clear" on display.
Confirm by pressing OK.
The timer will start deleting entries. The display will count off consecutive
numbers of deleted entries (from 1 to 500). Upon completion the display will
show "prog".
B. sys
Confirm selected option by pressing OK. The timer will enter standby mode
awaiting for deletion confirmation. This is indicated by alternating flashing
of "syr" and "clear" on display.
Confirm by pressing OK.
The timer will start deleting entries. Upon completion the display will show
"sys".
C. error
If the timer system detects an error, the display will show "error" message
at the root level. At the same time in the "clear" section the extra "error"
item will appear. Error reset is possible only through the menu (menu ->
syst -> clear -> error).
Confirm the “error” option by pressing OK. The timer will enter standby
mode awaiting for deletion confirmation. This is indicated by alternating
flashing of "error" and "clear" on display.
Confirm by pressing OK. The timer will reset the error. The display will show
“error”. The clock will return to standard operation mode.
5.7 System information – info
Confirm by pressing OK. The timer will enter the information menu. Browse
the information by pressing +/- keys:
*clock type
*software version
Confirm by pressing OK. The timer will display current parameter for time
zone (12/-12). Pressing +/- keys set time zone for the clock. Confirm by
pressing OK. Time zone for Poland is +1.
5.3 Battery charge indicator – batt
Confirm by pressing OK. The clock will display information about battery
charge level.
HIGH - fully charged, new battery.
GOOD - in good condition, provides long-term operation.
LOW - low battery level, recommended replacement.
EMPTY - discharged, it must be replaced immediately.
5.4 System clock time adjustment - cal
Time adjustment is the number of seconds by which the system clock is
adjusted per month. Setting range: +/- 300 seconds.
For example:
If the clock is fast 4 seconds per month, set the parameter value -4.
Confirm by pressing OK. The timer will display current parameter of time
adjustment. Press +/- keys to set desired number of seconds. Confirm by
pressing OK.
5.5 Display contrast - lcd
Setting the display contrast. Range: -3 (lowest) ... + 3 (highest).
Confirm by pressing OK. The clock will display the current contrast
parameter. Use the +/- keys to set the contrast parameter. Confirm by
pressing OK.
5.6 Resetting the commands, parameter settings and errors - clear
Confirm by pressing OK. The timer will enter the submenu (prog - sys - error).
Use the +/- keys to select reset option.
IN/OUT DESCRIPTION
3-4 timer power supply
CHANNEL 1
1 COM contact input
5 NO contact output
- “standard open” position
6 NC contact output
- “standard closed” position
CHANNEL 2
2 COM contact input
7 NO contact output
- “standard open” position
8 NC contact output
- “standard closed” position
3
4
1
5
6
AC/DC
CONNECTION SCHEME
INSTALLATION
1. Turn off the power.
2. Mount the timer on the TH rail in the distribution box.
3. Connect wires according to the diagram.
4. Connect receivers according to the diagram.
5. Set the correct date (see section 2) and time (see section 3).
6. Set individual switch-on time programs for receivers.
SPECIFICATIONS
power input 24÷264V AC/DC
current load 2×[<16A]
contact 2× separated 1NO/NC
up time of the clock 6 years
battery type 2032 (lithium)
up time of the display operation no information
the accuracy of the clock 1s
time error ±1s/24h
precision of program time setting 1min.
program memory cell 500
(2× 125 pairs of ON-OFF COMMANDS/CHANNEL)
power consumption 1.5W
operating temperature -20÷50°C
terminal 2.5 mm² screw terminals
tightening torque 0.4Nm
dimensions 2 modules (35mm)
mounting on TH-35 rail
ingress protection IP20
(for T=20°C)
L
N
2
7
8
CHANNEL 1
PROG
Mo
ş
1
ON
MENU
OK
+
1 2 3 4
5 6 7 8
ş
2
OFF
CHANNEL 2
BATTERY REPLACEMENT
User can single-handedly replace the battery. Detailed instructions with
pictures and videos can be found on the website www.fif.com.pl on the
subpage of the timer. Battery type: 2032 (lithium).
D151109