5.0 System Programming
System programming can be performed either by front panel program-
ming as shown below or via portable computer and the FCI Field Configura-
tion Program. See the FCP Software Training Guide, P/N 9000-0456.
5.1 MAIN Menu selections
CONFIG. where automatic configuration of the system is accomplished,
as well as all of the system global programming, input to output group
programming and NAC coding.
WALK/DRILL allows the user to select Audible or Silent Walk Test as well
as activating and de-activating the System Drill function.
I/O allows the user to activate (turn on) or de-activate (turn off) any
output in the system.
CLOCK selection supplies the options for programming the
system time, date, day/night weekend and holidays.
LOG options for manipulating the Event Log are display, print,
clear (buffer) and selecting to print only the sensitivity report.
INFO gives the user basic system information such as the current
firmware version, the last configuration date as well as the last menu
designation used during the last system configuration update.
5.1.1 Addresses/Default settings after Autoconfiguration
Sensors occupy Addresses 01-99 on the signaling line circuits. Sensors
are ion, photoelectronic, or thermal. They are latching and non-verified
when autoconfigured. Monitor/Control modules occupy Addresses 101-198.
The type of device assigned to a monitor module during autoconfiguration
depends on the address as shown below:
Address Device
100-149 Manual station
150-159 Supervisory switch
160-169 Waterflow switch
170 Silence switch
171 Reset switch
172 Fire Drill switch
173 Alarm/Acknowledge switch
174 Trouble/Supv. Acknowledge switch
175 Tornado switch
176-179 Tamper switch
180-184 Control panel
185-189 Remote zone
190-198 Normally open contacts
AOM modules are silenceable and activate on general alarm (day or night).
AOM modules modified by breaking off tabs are non-silenceable and activate on general alarm (day or night).
MAIN
WALK / DRILL
Level 1
I/O
Level 2
CLOCK
Time Date
Level 1
Wkend/Holiday
Level 4
LOG
Level 2
INFO
Level 1
CONFIG.
Level 4
7100
MENU STRUCTURE
VIEW
Level 2
9000-0447 25 of 43