6.0 Power Up Procedure
6.1. General
Ensure that all cables and optional modules (if any) are installed and secured per the installation instructions.
DO NOT install any field wiring at this time. Connect the End of Line devices to the notification appliance and
municipal (if installed) circuits.
2. Power the panel with AC first. The system will initialize and indicate a “Battery Missing” condition.
3. Connect the batteries, taking care to observe polarity.
4. The system should be in normal condition. You may proceed with the installation of field wiring. Check all
wiring prior to connection to the control panel. Do not use this panel as a circuit tester.
6.2 To set the system time (Keyswitch must be engaged).
Press the MENU/Back button on the keypad and enter the Level 1 password, XXXXXX.
2. Press the OK button.
3. The Main Menu will be displayed. Press the Number 4 and the Clock Menu will be displayed.
4. Number 1 opens theTime setup. Number 2 opens the date setup, Number 3 opens the Day/Night setup.
Number 4 opens the Weekend setup, and Number 5 opens the Holiday setup. The data is entered by using
the keypad and the OK button when each section is completed. The OK button acts as an Enter Key.
5. Press the Reset/Lamptest button and ensure that the time and date remain correct.
6.3 Automatic Configuration
1. Press the Menu/Back button on the keypad and enter the Level 4 password, YYYYYY.
2. Press the OK button.
3. The Main Menu will be displayed. Press the Number 1 and the Configuration Menu will be displayed.
4. Press the Number 1 to open the Automatic Configuration Menu. Numbers 2 through 5 are for specific
programming and are covered in previous sections.
5. Since this is the first time the system is being configured, press the Number 1 to initiate the Clear,Then
Configure process. This will place all of the system settings to the factory default and then read all of the
devices correctly connected to the two SLCs. After this process is complete the system may be given an initial
test to assure all of the devices have been installed into the system memory.
NOTE: Automatic configuration does not set the DACT. The DACT must be programmed.
40 of 43 9000-0447
Technical Manuals Online! - http://www.tech-man.com