17.0 REMOTE ZONE ANNUNCIATION
17.1 Remote zone annunciation with Zone Detector Module (ZDM)
or Verification Zone Module (VZM)
BMFC Terminals 36 and 41 are provided for connection of a supervised remote zone annunciator with either
LED or incandescent lamp. Should an open in the field wiring or annunciator occur, a zone and system trouble
will activate. Connect as follows:
1) Cut JRA, JRB (on BMFC or ZMC) for each zone annunciated.
2) If an FCI LED annunciator is used, go to Step 4.
3) If an incandescent lamp annunciator is used, ensure that the corresponding zone(s) on the BMFC and/or
ZMC is configured as follows:
BMFC - J31 (Zone 1) and/or J32 (Zone 2) Install a jumper.
ZMC - J11A (Zone 3, 5 etc.) and/or J11B (Zone 4, 6 etc.) Install a jumper.
4) Connect the annunciator common to Terminal 41 between Zones 1 and 2.
5) Connect the individual LED/lamp wires to Terminal 36 of each zone annunciated.
17.2 Remote Zone Annunciation With Double Density Zone Detector Module (ZDM-D)
Terminals 34, 35, and 41 are provided for connection of supervised remote zone annunciators, either LED
or incandescent lamp. Should an open in the field wiring of an annunciator occur, a zone (Zone A or Zone B)
and system trouble will activate. Connect as follows:
1) Cut W1 for Zone A, or W2 for Zone B (jumpers are located on ZDM-D).
2) Connect the annunciator common to Terminal 41 between Zones 1 and 2.
3) Connect the individual LED/lamp wires to Terminal 35 for ZDM-D Zone A, and Terminal 34 for Zone B
for each zone annunciated.
18.0 ACCESSORY ZONE SIGNAL OUTPUT
A. Alarm by Zone Output - Terminal 42.
This is to be used only with FC-72 series accessories, SRB-6, RB-6, etc. It provides a power limited 24 VDC
alarm output per zone.
B. Trouble-By-Zone Output - Terminal 47.
This is to be used only with FC-72 series accessory, trouble by zone board (TBZ/TBZ-U). It provides a power
limited 24 VDC trouble output per module.
IMPORTANT - When an incandescent lamp annunciator is used, only #1820 lamps (28 VDC/0.100 A) or #1829
lamps (28 VDC/0.070 A) are to be used. Microfuse F1, P/N 4300-0018, for Zone A, or Microfuse F2, for Zone B,
on the ZDM-D MUST be installed. (Consult factory for assistance).
NOTE: When using ZDM-D module, Terminal 33 is used as alarm output for Zone A and Terminal 42 for Zone B.
(See Figure 17)
NOTE: Do not connect any external devices to these terminals.
IMPORTANT - When an incandescent lamp annunciator is used, only #1820 lamps (28 VDC/0.100 A) or #1829
lamps (28 VDC/0.070 A) are to be used. F1 microfuse, P/N 4300-0018, MUST be installed in socket W2
of the ZDM or VZM. (Consult factory for assistance).