Supv. Alarm Total Supv. Total Alarm
Qty Model Description Current Current Current Current
1 FC-72-1 1 Zone Control Panel .063 A .370 A(*) .063 A .370 A
BMFC-6 Basic Master Fire Card (*) (*) —— ——
ADAM-6-1 Aux. DC Actuation Module .013 A .073 A
ADAM-6-2 Aux. DC Actuation Module .026 A .133 A(#)
APS-6 Aux. Power Supply .020 A —— ——
AVM Alarm Verification Module .012 A .030 A
BCM-6 Notification Appl. Circuit Module (**) (**) —— ——
BMC-6 Master Coder Module (**) (**) —— ——
BCM-6 Notification Appl. Circuit Module (**) (**) —— ——
TCM-6 Temporal Pattern Module (**) (**) —— ——
PNIS PNIS Zone Coder Module .004 A/zone .150 A
PS-6 Power Supply —— —— —— ——
RB-6 Aux. Relay Module —— .070 A (#) ——
RDF Releasing Device Interface .002 A .047 A
RRT Remote Reset Capability (##) (##)
RTI Remote Trouble Indicator .002 A .002 A
RZA Remote Zone Annunciator (LED) —— .002 A ——
SRB-6 Supervised Aux. Relay Module .019 A .079 A (#)
TBZ Trouble By Zone Module .003 A .021A/zone
TDS438 Time Delay Switch —— .001 ——
VZM Verification Zone Module .010 A .175 A
WTM Walk Test Module —— .040 A ——
ZMC Zone Mother Card —— —— —— ——
ZDM Zone Detector Module .006 A .163 A
ZDM-D Zone Det. Module, Dual Density .018 A .298 A (#)
CPD-7051 Smoke Det., Ionization .00005 A ⊕ ——
PSD-7155/
PSD-7156 Smoke Det., Photoelectric .00005 A ⊕ ——
SBS-1101 Smoke Det., Ionization .00010 A ⊕ ——
SBS-1201 Smoke Det., Photoelectronic .00012 A ⊕ ——
301 Series Smoke Det. .00012 A ⊕ ——
4WSD 4 Wire Smoke Det/EOL Relay
NOTES: (*) FC-72-1 contains BMFC-6, PS-6, one ZDM and one BCM-6, BMC-6, TCM-6, or CCM-6.
(**) Included in BMFC-6 and/or ADAM-6. Power requirements are as above.
(#) With both circuits in alarm.
(##) Consult factory.
⊕ Alarm current is limited by zone module circuitry and is not involved in battery calculation.
Modules DMM, ABM and DBM do not consume current and are not involved in calculations.
Table 2 FC-72 System Battery Standby Calculation Chart
A Total Supv. Current from above chart
B Enter number of standby hours (24 hrs for NFPA Local, Proprietary,
Central Station, 60 hrs for NFPA Auxiliary, Remote Station,
90 hours for FM Deluge/Preaction)
C Multiply Line A times hours in Line B—enter
D Total alarm current from above chart
E Enter alarm sounding period in hours. (5 minutes = .084 hr.)**
F Multiply Line D times Line E —enter
G Total of Lines C&F—enter
H Multiply Line G by 1.2 — enter (Total ampere/hours required*)
* Use next size battery with capacity greater than required.
**5 minute alarm period for NFPA, 10 minute period for FM Deluge/Preaction Service
Battery Calculations