BLUEHELIX TECH RRT 24 H
198 EN
cod. 3541C662 - Rev. 00 - 09/2020
F56 - A56
Calibration fault
Incorrect parameters
Check parameters and carry out a 100% calibra-
tion
Electrode damaged or not correc-
tly positioned.
Check the position of the electrode, replace it if
necessary. After replacement, repeat the 100%
calibration
Recirculation of fumes inside the
boiler
Check the tightness of the flue pipe and the seal
of gaskets
Calibration procedure not com-
pleted
Poor primary circuit circulation or
poor dissipation during calibration
Reset the fault. Turn on the hot water faucet and
wait for the flame to stop flashing (about 2 minu-
tes)
F61 - A61 Controller AGC01 fault Controller AGC01 internal error
Check the ground connection.
Check the electrode.
Repeat the 100% calibration procedure.
If necessary replace the control unit.
A63 Controller AGC01 fault
Unstable power supply Check the power supply
Controller AGC01 internal error If necessary replace the control unit
A54 - A55
F62 - F63
Combustion fault
Insufficient system gas pressure Check the gas supply pressure
Unstable grid voltage Check the supply voltage
Electrode damaged or not correc-
tly positioned
Check ignition electrode and ground
Turn off power supply for 10 seconds, reset the
fault and perform a 100% calibration (Sc15=1).
F67 BCC Service key connected Load the parameters
F68 - A68 BCC Service key error
Error loading BCC Service key
file
Repeat the loading procedure within 5 minutes
from the boiler power supply and replace the
BCC Service key if necessary
A62
No communication between
controller and gas valve
Controller not connected Connect the controller to the valve
Valve damaged Replace valve Check the wiring or replace the valve
A64
Maximum number of consecu-
tive Resets exceeded
Maximum number of consecutive
Resets exceeded
Disconnect the power supply to the boiler for 60
seconds and then reinstate the boiler
F66 Firmware not loaded successfully Reload the firmware or replace the card
Fault code Fault Possible cause Cure

Table of Contents

Other manuals for Ferroli BLUEHELIX TECH RRT 24 H

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ferroli BLUEHELIX TECH RRT 24 H and is the answer not in the manual?

Ferroli BLUEHELIX TECH RRT 24 H Specifications

General IconGeneral
BrandFerroli
ModelBLUEHELIX TECH RRT 24 H
CategoryHeater
LanguageEnglish

Related product manuals