EasyManua.ls Logo

Filtrine QCP - User Manual

Default Icon
2 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
QCP INSTALL]
REV. 03.15.19
Filtrine Mfg. Co. • 15 Kit St. Keene, NH 03431 USA
800-930-3367 • 603-352-5500 • FAX 603-352-0330
WEB www.filtrine.com • EMAIL cool@filtrine.com
FILTRINE IS ISO 9001:2015 CERTIFIED
PRODUCT LINE APPROVED MARK AVAILABLE
MADE IN USA
Please read these instructions completely before installation.
INSTALLATION INSTRUCTIONS
The QCP Quick Connect Panel provides all the diagnostics that
medical equipment manufacturers require.
Mount the QCP panel in a location where meters can be
read by the medical equipment operators. Consideration
should be given to the routing of chilled liquid line.
Excessive pipe lengths cause heat gain as well as pressure
reduction. Locate the panel between the chiller and medical
equipment, preferably close to the medical equipment. The
closer the panel is to the medical heat exchanger, the more
useful the temperature readings will be.
All coolant lines must be insulated to reduce heat gain and
to prevent condensation from forming during high humidity
conditions.
The piping procedure simply consists of matching QCP
connections to the appropriate points and setting the ball
valves to the desired operation mode. (See Operation
Modes table on page 2.)
If plumbing line size reduction is being considered, it
must be veried that proper ow and pressure can be
maintained. As a general rule, reducing the pipe size is not
recommended.
When installation has been completed, put the unit in Full
Bypass Mode. Close the ball valve that feeds the city water
drain while lling the system. If this valve is left open while
the chiller is inoperative and being lled, the uid being
added to the system will run down the drain. Once the chiller
has been started, open this valve.
A list of plumbing/electrical connections to the QCP panel
and where they should be routed:
CITY WATER DRAIN* This connection is piped to a oor
drain or any other suitable water
disposal drain.
TO CHILLER Piped to the RETURN connection
at the chiller.
FROM CHILLER Piped to the chiller DISCHARGE
connection.
CITY WATER SUPPLY* Connect to the municipal water
supply for backup cooling.
FROM EQUIPMENT Piped to the discharge line of the
medical equipment.
SOLENOID COILS* Connect the wires in parallel and
refer to the chiller electrical dia-
gram.
* Optional equipment for QCP-AS
OPERATION
Your QCP will give you years of trouble-free service. Like any
other piece of ne equipment, occasional maintenance may
be required. You will soon discover the exibility designed into
the QCP. In most circumstances, service can be performed on
the unit or chiller without interrupting medical requirements.
There are ve operation modes of the QCP panel summa-
rized below:
1. NORMAL
OPERATION
The standard operating conguration. See
Mode 1 on next page and note location/
settings of valves and ow paths.
2. FULL
BYPASS
This conguration isolates the chiller from
the medical equipment. It can be used when
starting the chiller if the medical equipment
is not yet operational. The chilled water is
simply routed from the chiller discharge
back to the return line. See Mode 2 in chart
on next page and note location/settings of
valves and ow paths.
3. SERVICE
FLOW
METER
In the event the ow meter or other instru-
ments in this path need service, ow can
be routed as shown. See Mode 3 in chart
on next page and note location/settings of
valves and ow paths.
4. SERVICE
FILTER
Filter changes will be required when the
system is initially started and periodically
thereafter. This mode allows uninterrupted
service to the medical equipment while a l-
ter change takes place. See Mode 4 in chart
on next page and note location/settings of
valves and ow paths.
5. CITY
WATER
BACKUP*
This condition will occur if the chiller fails
and actuates solenoids 1 and 2. Notice that
the ow of water is from the city water con-
nection through the medical equipment
and down the drain. IMPORTANT: The city
water pressure must not exceed 80 p.s.i.
The automatic backup will only work if the
system was previously operating in Mode 1
(Normal Mode). See Mode 5 in chart on next
page and note location/settings of valves
and ow paths.
* Optional equipment for QCP-AS
Charts on reverse
FILTRINE QCP – QUICK CONNECT PANEL
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
Question and Answer IconNeed help?

Do you have a question about the Filtrine QCP and is the answer not in the manual?

Overview

The Filtrine QCP (Quick Connect Panel) is a diagnostic and control panel designed for use with medical equipment, particularly those requiring chilled liquid. It provides essential diagnostics and allows for flexible operation and maintenance without interrupting critical medical procedures.

Function Description:

The QCP acts as an intermediary between a chiller and medical equipment, managing the flow of chilled liquid and providing crucial diagnostic information. It is equipped with various valves, gauges, a flow meter, and a filter to ensure optimal performance and system integrity. The panel's primary function is to facilitate the continuous and reliable supply of chilled liquid to medical equipment, even during maintenance or in the event of a chiller failure.

Usage Features:

The QCP offers five distinct operation modes, providing significant flexibility in managing the chilled liquid system:

  • 1. Normal Operation: This is the standard operating configuration where chilled liquid flows from the chiller, through the QCP, to the medical equipment, and then returns to the chiller. This mode ensures continuous cooling under normal conditions.
  • 2. Full Bypass: In this mode, the chiller is isolated from the medical equipment. Chilled water is routed directly from the chiller discharge back to its return line. This is useful for starting the chiller when the medical equipment is not yet operational or for performing maintenance on the chiller itself without affecting the medical equipment.
  • 3. Service Flow Meter: This mode allows for servicing or replacement of the flow meter or other instruments in its path. The flow of chilled liquid is rerouted to bypass these components, ensuring that medical equipment continues to receive cooling without interruption.
  • 4. Service Filter: This mode is crucial for routine maintenance, enabling filter changes without interrupting the flow of chilled liquid to the medical equipment. The system is designed as a closed loop, which, over time, reduces contamination and the frequency of filter changes.
  • 5. City Water Backup (Optional): This critical safety feature automatically activates if the chiller fails. In this mode, city water is routed through the medical equipment and then to a drain, providing backup cooling. It's important to note that the city water pressure must not exceed 80 p.s.i. This automatic backup only functions if the system was previously operating in Normal Mode.

Installation Considerations:

  • The QCP panel should be mounted in a location where its meters are easily readable by medical equipment operators.
  • Consideration must be given to the routing of the chilled liquid line. To minimize heat gain and pressure reduction, the panel should be located between the chiller and medical equipment, preferably close to the medical equipment. Closer proximity to the medical heat exchanger provides more useful temperature readings.
  • All coolant lines must be insulated to prevent heat gain and condensation, especially in high humidity environments.
  • Piping involves matching QCP connections to the appropriate points and setting ball valves according to the desired operation mode.
  • Reducing pipe size is generally not recommended as it can compromise proper flow and pressure.
  • Upon completion of installation, the unit should be set to Full Bypass Mode. When filling the system, the ball valve feeding the city water drain should be closed to prevent fluid from draining if the chiller is inoperative. This valve should be opened once the chiller has started.

Plumbing/Electrical Connections:

  • City Water Drain (Optional): Piped to a floor drain or other suitable water disposal drain.
  • To Chiller: Piped to the RETURN connection at the chiller.
  • From Chiller: Piped to the chiller DISCHARGE connection.
  • City Water Supply (Optional): Connects to the municipal water supply for backup cooling.
  • From Equipment: Piped to the discharge line of the medical equipment.
  • Solenoid Coils (Optional): Wires connected in parallel, referring to the chiller's electrical diagram.

Maintenance Features:

  • Filter Maintenance: The QCP uses a bag-type filter, typically a 50-micron bag. A new filter has a pressure drop of less than 5 p.s.i. The filter should be changed if the pressure drop across the unit exceeds 12 p.s.i. A spare filter should always be kept on hand. The "Service Filter" mode allows for filter changes without interrupting medical equipment operation.
  • Closed-Loop System: The system is designed as a closed loop, which helps to clean the coolant of contamination over time, making filter changes less frequent.
  • Contamination Indicators: If repeated city water operation is actuated, filter contamination is likely, and the filter element should be changed if the pressure drop across the unit exceeds 12 p.s.i.g.

Technical Specifications:

  • Filter Type: Bag type, 50 micron.
  • New Filter Pressure Drop: Less than 5 p.s.i.
  • Filter Change Threshold: Pressure drop across the unit exceeds 12 p.s.i.
  • City Water Pressure Limit (Backup Mode): Must not exceed 80 p.s.i.
  • Certifications: Filtrine is ISO 9001:2015 Certified, Product Line Approved, CE Mark Available.

The Filtrine QCP is designed for years of trouble-free service, offering a robust and flexible solution for managing chilled liquid systems in critical medical environments.

Filtrine QCP Specifications

General IconGeneral
BrandFiltrine
ModelQCP
CategoryDiagnostic Equipment
LanguageEnglish