Programming Options
36
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Ademco Contact ID Format
If 'E' is entered for address 16, the following data is automatically programmed for the Primary phone number event
codes. Enter '000' for the data setting to disable the report.
Notes:
1.
Zero entries prevent the transmission of the report to the Central Station
2.
Refer to Contact ID program locations 64 - 68
3.
The identification of the zone/sensor number is automatically transmitted by the UDACT-F and is added to the
main event code. Refer to Table A-3, “Ademco Contact ID Reporting Structure,” on page 49, for additional
information
4.
Factory default for this report is 110 (110 is transmitted for modules, however, 111 will automatically be trans-
mitted for smoke detectors). Use Type Mode (refer to “Type Mode” on page 44) to change this report per zone
or point
TAB L E 3- 4 : Ademco Contact ID Primary Number
Address Description Setting
1
Sensor Number
69 - 71 Primary # General Alarm Code 110
000
2
72 - 74 Primary # Zone/Point Alarm Code
110
4
Note
3
75 - 77 Primary # General Supervisory Code 200
000
2
78 - 80 Primary # Zone/Point Supervisory Code 200
Note
3
81 - 83 Primary # General Fault Code 300
84 - 86 Primary # AC Fault Code 301
87 - 89 Primary # Zone/Point Fault Code 380
Note
3
90 - 92 Primary # Low Battery Fault Code 302
93 - 95 Primary # Telco Primary Line Fault Code 351
96 - 98 Primary # Telco Secondary Line Fault Code 352
99 - 101 Primary # NAC Fault Code 321
102 - 104 Primary # Communication Trouble Primary # Code 354
105 - 107 Primary # Communication Trouble Secondary # Code 354
108 - 110 Primary # 485 Communication Trouble Code 300
111 - 113 Primary # System Off Normal Code 308
114 - 116 Primary # UDACT-D Off Normal Code 350
117 - 119 Primary # System 24 Hour Test 602
120 - 122 Primary # System 24 Hour Test with Active Event 608
123 - 125 Primary # Manual Test Message 601