EasyManuals Logo

Fireye MicroM MEC120R User Manual

Default Icon
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #37 background imageLoading...
Page #37 background image
37
3. Manually shut off all fuel and observe the loss of flame signal on the test meter.
4. If flame signal does not reduce to zero within the flame failure response time of the control
(FFRT determined by the selection of the amplifier), verify the UV flame detector is not actu-
ated by the ignition spark. If spark is detected, a metallic shield or relocation of the UV detector
is required.
5. IMPORTANT: When the test is completed, reconnect the spark ignition to Terminal #4.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fireye MicroM MEC120R and is the answer not in the manual?

Fireye MicroM MEC120R Specifications

General IconGeneral
BrandFireye
ModelMicroM MEC120R
CategoryControl Unit
LanguageEnglish

Related product manuals