Fault 3: 3 beeps
Reason: The resistance of FC sensor is outside the normal range (> 45K Ohms)
Primary Action: Check the 4-way connector at the control module.
Secondary Action: Check sensor resistance.
Reterminate the 4-way connector.
Tertiary Action: Replace control module.
Fault 4: 4 beeps
Reason: The resistance of FC sensor is outside the normal range (< 660 Ohms)
Primary Action: Check the 4-way connector at the control module.
Secondary Action: Check sensor resistance.
Reterminate the 4-way connector.
Tertiary Action: Replace control module.
Fault 7: 7 beeps
Reason: The resistance of defrost sensor is outside the normal range (> 45K Ohms)
Primary Action: Check the 4-way connector at the control module.
Secondary Action: Check sensor resistance.
Reterminate the 4-way connector.
Tertiary Action: Replace control module.
Fault 8: 8 beeps
Reason: The resistance of defrost sensor is outside the normal range (< 660 Ohms)
Primary Action: Check the 4-way connector at the control module.
Secondary Action: Check sensor resistance.
Reterminate the 4-way connector.
Tertiary Action: Replace control module.
Fault 9: 9 beeps
Reason: Compressor has failed to start after 5 attempts
Primary Action: Check the integrity of the compressor
Secondary Action: Replace control module.
Fault 10: 10 beeps
Reason: The control variable resistor has an open circuit fault.
Primary Action: Check the continuity of the circuit between the variable resistor and the control
module and the connections at the variable resistor and the control module.
Secondary Action: Replace control module