Power Logger
Specifications
29
Temperature coefficient:
±0.1 % of the measured value per K.
Intrinsic error:
Refers to reference temperature, max. deviation is
guaranteed for 2 years.
Operating error:
Refers to operating temperature range, max. deviation is
guaranteed for 2 years.
Climatic class: C1 (IEC 654-1) -5 °C to +45 °C, 5 % to 95 % RH, no dew
Housing:
Cycoloy shock and scratch proof thermoplast V0-type (non-
flammable) with rubber protection holster
EMC
Emission: IEC 61326-1:2006 class B
Immunity: IEC 61326-1:2006
Power supply: NiMH battery-pack, with ac adapter (15 V to 20 V/0.8 A)
Operation time with
battery:
Typical >8 h with bright backlight, >10 h with low backlight,
and 24 h without backlight
Dimensions: 240 x 180 x 110 mm (6.1 x 4.6 x 2.8 in)
Weight: 1.7 kg (3.75 lb), including battery
Safety
Safety:
EN/IEC 61010-1:2001 (2
nd
ed.) 600 V CAT III, double or
enforced insulation
Pollution Degree: 2
Protection:
IP65; EN60529 (refers only to the main housing without the
battery compartment)
RMS values are measured with a 20 ms resolution.
V-RMS Wye Measurement
Measuring range:
57 / 66 / 110 / 120 / 127 / 220 / 230/ 240 / 260 / 277 / 347 /
380 / 400 / 417 / 480 V AC
Intrinsic error:
±(0.2 % of measured value. + 5 digits)
Operating error:
±(0.5 % of m. v. + 10 digit)
Resolution: 0.1 V
V-RMS Delta Measurement
Measuring range:
100 / 115 / 190 /208 / 220 / 380 / 400 / 415 / 450 / 480 / 600 /
660 / 690 / 720 / 830 V AC
Intrinsic error:
±(0.2 % of m. v. + 5 digit)
Operating error:
±(0.5 % of m. v. + 10 digit)
Resolution: 0.1 V
A-RMS Measurement
Flexi Sets and current probes with voltage output are supported. All current probes must
correspond to 600 V / CAT III