SMFT-1000
Calibration Manual
14
Range
Test Vo l tag e
[V]
Te s t Po i n t s
[M
Ω]
Display Readings [M
Ω]
Lower Upper
0.2 M
Ω to 99.99 MΩ
500
0.25 0.19 0.31
0.50 0.43 0.58
3.00 2.80 3.20
30.00 28.45 31.55
50.00 47.45 52.55
95.00 90.20 99.80
100 M
Ω to 199.9 MΩ
112.0 100.3 123.7
160.0 143.5 176.5
180.0 161.5 198.5
200 M
Ω to 999 MΩ
260 203 317
750 595 905
830 659 1001
0.2 M
Ω to 99.99 MΩ
1000
0.25 0.19 0.31
1.00 0.90 1.10
6.00 5.65 6.35
50.00 47.45 52.55
90.00 85.45 94.55
95.00 90.20 99.80
100 M
Ω to 199.9 MΩ
112.0 100.3 123.7
160.0 143.5 176.5
180.0 161.5 198.5
200 M
Ω to 999 MΩ
260 203 317
750 595 905
830 659 1001
Tab le 5 . R
INS
Method I (No Voltage) Test Points (cont.)