Service Manual
9.1.5. Comp. Locked: locked compressor alarm
see
par.4.4
par.7.2.1
1
see
par.9.1.4
The locked compressor alarm (Locked Comp.) appears on the display when the refrigerant temperature at condenser output,
read by the “NTC probe condenser”, is higher than parameter C7 for the C8 time. The alarm is recorded in the Service menu,
under Alarms.
see the component and parameter table
The Comp. Locked alarm stops the M1” compressor and the “M3” evaporator fans
See “OVERHEAT. COND. overheated condenser alarm” to run diagnostics
After identifying and resolving the cause of the alarm, it is necessary to disconnect
and reconnect the power supply to the equipment and resume normal operation