Parameters overview | 4
B1820023_en | Service handbook Lambdatronic H 3200 - T4e 47
4.1.6 Heating - General settings
System menu Heating General settings
service
Correction value for external sensor
If it is found that the evaluated value for the outside
temperature value deviates from the displayed value, the
evaluation of the outside temperature sensor can be
adjusted using this parameter. The temperature measured
by the sensor is increased (positive value) or reduced
(negative value) by the pre-set value.
Heating circuit module to which the external
sensor is connected (0 = core module)
If the outside temperature sensor is not connected to the
core module, the address of the relevant heating circuit
module +1 must be set here (sensor 1 on relevant
module).
Using room sensor inputs for room thermostat
NOTICE!This parameter influences all sensor
connections to which an analogue room temperature
sensor can be connected!
▪ NO: At the sensor connector of the room sensor, a
room sensor must be connected to control the room
temperature.
▪ YES: At the sensor connector of the room sensor, room
thermostats can be connected to control the room
temperature.
Contact of room thermostat open: Heating circuit pump
deactivated, mixing valve is closed
Contact of room thermostat closed: Heating circuit pump
and mixer control active
4.2 Water
4.2.1 Water - Status
DHW tank top temperature
Current temperature of the DHW tank. If the time window
for DHW tank loading is reached and the temperature falls
below the value set under parameter “Reload if DHW
tank temperature is below“, the DHW tank will be
loaded. The DHW tank is loaded either until the time
window has elapsed or the temperature set under
“Desired DHW tank temperature“ has been
reached.
DHW tank bottom temperature
Prerequisite: Solar panel system is regulated by Froling!
Current temperature in the area of the reference sensor of
the solar panel system.
DHW tank pump control
Specifies the speed of the DHW tank pump as a
percentage of maximum speed.