5.4.4 Clean the particle filter (optional) and heat exchanger pipes
NOTICE! Remove the particle filter before cleaning the heat exchanger.
Remove and clean the particle filter (optional)
For all electrodes and housings of the particulate filter compliance with the following
steps is mandatory:
Undo two screws and remove the lower cover
Unplug the high-voltage cable (A) from the isolator and disconnect the vibration
motor plug connection (B)
Remove the cover plate between the e-filter and the stoker
Undo the external screws on the cover and carefully remove the entire unit
CAUTION: In so doing, pay special attention to electrode (C).
Undo the external screws on the cover and carefully remove the entire unit
CAUTION: The electrodes (C) require special attention!
Up to boiler type 60:
Starting at boiler type
80:
5
Servicing the system
Maintenance work by technicians
64 Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com