FROMM
CH12-TI-FS250.EN10
How to change the inverters parameters.
When the inverter is in running mode the LED on is FREF (1)
In order to enter in programm mode push the cycle button (2) until the LED PRGM (3) becomes ON
On the display there is now n01, in order to enter another parameter push on the button (4) and (5)
Pushing the button (6) we enter in the actual parameter program, in order to change the values use
the buttons (4) and (5) and memorize it with (6)
With the button (2) you can turn-off the LED PRGM (3) and turn-on FREF (1)
STANDARD INVERTER SETTINGS
INVERTER OMRON SETTINGS
Turntable Carriage Pre - stretch
N01 Initialization 1 1 1
N02 Selection for the run control 1 1 1
N03 Selection for reference frequency 2 2 2
N09 Max. output frequency 55.00 60.00 90
N10 Max. voltage 230 230 230
N16 Acceleration ramp time 6.00 0.3 0.3
N17 Deceleration ramp time 3.00 0.1 0.3
N30 Upper output frequency limit 100 100 100
N31 Lower output frequency limit 8 30 0
N40 Assignment for the multifunctional exit 0 0 0
After installation of a NEW inverter please do not forget to start the inverter
first!
Otherwise the inverter will never work!!!
Start up procedure to decrease the intervent threshold with alarm Uul
N01 = 15
N97 = 2 + 10 = 12
N01 = 20
N01 = 12
Usefull to know !
Before maintenance ore trouble shooting always check the digital inputs of the machine. No digital
input mostly the connect switch is broken en has to be replaced. Always check the connections very
thoroughly.